Conmutando 500 kV

Siempre que veo este video me emociono :D




Según el primo del cuñao del tío que sujetaba la cámara, que le mandó un mail al que puso este videlo en el tubo, la explicación científica viene a ser:

" The video was taken at Eldorado Substation in Boulder City, NV. The file is called Lugo because this switch and shunt reactor are on the line that goes to Lugo. Thisone is clearly a 500KV (I can tell by the size) three-phase switch, probably rated atabout 2000 amps of normal current carrying capability. 500 KV refers to the phase-to-phase voltage. Divide by 1.732 to get the phase-to-ground voltage (289 KV).

This type of switch typically is used at one end of a transmission line, in some cases inconjunction with or instead of a circuit breaker for a variety of different configurationreasons that vary greatly from one utility to the other. Or, it may be used to connect alarge transformer to the system.

In this case, the switch is being used to connect a special kind of transformer. The 3 single-phase transformers can be seen behind the truck. I say transformer, but as you can see, they have leads going in, but not coming out. These are actually single winding inductors connected from phase to ground and are commonly called "shunt reactors." These inductors are installed to offset the capacitive effects of un-loaded transmisión lines, When a long 500 KV or 765 KV line is energized from one end, its inherent capacitance causes an unacceptable voltage rise on the open end of the line. The "shunt reactor" is installed to control that open-circuit voltage. Where current into the capacitor component of the line impedance leads voltage by 90 degrees, current into the shunt reactor lags voltage by 90 degrees. I have since learned that these shunt reactors are rated at 33.3 MVAR each to make up a 100 MVAR bank.

The switch being opened is called a "circuit switcher." It consists of two series SF6 gas puffer interrupters (similar to a circuit breaker) and an integrated center-break disconnect. The interrupters are to the right of the switch blades. They just look like gray porcelain insulators. At 345 and 500 KV these types of switches typically have two interrupters per phase in series in order to withstand the open circuit voltaje encountered when de-energizing a line or transformer. They rely on synchronized opening of the two interrupters and voltage even distributed across the two interrupters by "grading" devices (typically lots of series capacitors or resistors).

The way they are supposed to work is the interrupters both trip, grading capacitors or resistors cause the open circuit voltage to split evenly across the two interrupters, the switch blades open with no current flow, and the interrupters close as the switch reaches the full open position. I originally titled this very BIG capacitor because that is what unloaded transmission line looks like. The parallel wires have a huge capacitive effect between ground and each other. On a 500KV line like this the current (leading the voltage by 90 degrees) required to energize this capacitor is approximately 1.8 amps per-mile of line per phase. That's 1.8 amps per phase at 289KV, or about 1.56 Mega Vars (million volt amps reactive) per mile. However, we are actually looking at the shunt reactor current which is inductive and lags the voltage by 90 degrees. So, I should have said "very big inductor."

The switch operation you see in this video in my opinion is a failed attempt to interrupt that inductive current. The failure appears to be that the far right interrupter does not open or the grading device has failed. The voltage across the remaining open interrupter exceeds the rating and it flashes over (you can see the first arc develop across one interrupter). Therefore, the switch blades are left to interrupt the current (not designed to do that) as they open. As the interrupter closes you can see the arc across it go out. However, the arc across the switch gets as tall as a 3 story building. The arc is extinguished only when the circuit breaker energizing the line, circuit switcher, and reactor is opened by the operator. Because some trouble was expected on the switch, arrangements had been made ahead of time to trip open the circuit breaker if necessary. This is the only failure I have ever seen where the arc lasted so long and grew so large without first going phase-to-phase or phase-to-ground taking the circuit out of service. It just keeps growing straight up where it contacts nothing. "


Comments:
Solo magneto podria hacer algo así!!!
Y nosotros, meros homo sapiens lo hemos imitado!!

larga vida a lso ingenieros!!!

Tio, me cuesta mazo entender todo lo que pones. Es un idioma extraño para mi
 
Me alegro del regreso ;)
 
no es un idioma extraño, Freiji, es ingles :P
 
Publicar un comentario



<< Home

This page is powered by Blogger. Isn't yours?